K109S - V/I Converter With Power For 2 Wires Transducers

 

 

 

K109S is a device that accepts mA/V signals able to convert it into mA/V standard signals. 
The device can power also all 2-wire sensors and all parameters are confi gurable through dip-switches.
The power supply connection is available on the terminals or a special connector (K-BUS) allows
a distribution of the power supply to the modules via bus connector. A 3-way galvanic isolation
among Power supply // input // output circuits assures the integrity of your datas.

 

General Data
  • Power supply: 19,2…30 Vdc
  • Power consumption: 500 mW
  • Isolation: 1.500 Vac (3 way)
  • Transducer Power Supply: Yes
  • Accuracy: 0,1%
  • Response time: 40 ms
  • Status Indicators: Power supply, error
  • Setting: Dip Switches
  • Mounting: 35 mm DIN rail guide
  • Protection Degree: IP20
  • Operating Temperature: -20..+65 °C
  • Dimension (W x H x D): 6,2 x 93 x 102,5 mm
 
Input
  • Channel Numbers: 1
  • Voltage:

- Range: 0..10 / 10..0 / 0..5 / 1..5 V              

- Impedance: 110 kΩ

  • Current:

- Range: 4..20 / 20..4 / 0..20 / 20..0 mA (active or passive input)
- Impedance: 35 Ω

 
Output
  • Channel Numbers: 1
  • Voltage:

- Range: 0..10 / 10..0 / 0..5 / 1..5 V
- Min load resistance: 2 kΩ

  • Current:

- Range: 4..20 / 20..4 / 0..20 / 20..0 mA
- Max load resistance: 500 Ω
- Protection: 25 mA

 
 
Standard
  • Approval: CE
  • Norms: EN 50081-2; EN 55011; EN 50082-2; EN 61000-2-2/4; EN 50140/141; EN 61010-1