Micropilot FMR53 - Radar Measurement Time-of-Flight
Micropilot FMR53 for simple level measurement applications in liquids. With its slim rod antenna, FMR53 free space radar is particularly suited for small process connections. The PTFE coating of the rod antenna and flange plating guarantee resistance also in aggressive media. The Micropilot FMR53 is used for continuous, non-contact level measurement of liquids, pastes and slurries. The measurement is not affected by changing media, temperature changes, gas blankets or vapors.
Benefits
-
Reliable non-contact measurement even for changing product and process conditions
-
HistoROM data management concept for fast and easy commissioning, maintenance and diagnostics
-
Highest reliability even in the presence of obstructions in the vessel due to new Multi-Echo Tracking evaluation
-
Hardware and software developed according to IEC 61508 up to SIL3 (in homogeneous redundancy)
-
Seamless integration into control or asset management systems
-
Intuitive, menu-guided operation concept (on-site or via the control system)
-
World's easiest proof test concept for SIL and WHG saves time and cost
Field of application
Especially suited for small process connections, PTFE sensors usable in chemically aggressive media.
-
Process connections: Thread or flange
-
Temperature: -40 to +150°C (–40 to +302°F)
-
Pressure range: -1 to +40bar (–14.5 to +580psi)
-
Maximum measuring range: 20m (66ft)
-
Accuracy: ±6mm
-
C-band: 6GHz
-
International explosion protection certificates, 5-point linearity protocol, WHG overfill prevention, SIL
Features and specifications
| Measuring Principle | Level radar | |
| Characteristic / Application |
For common non-contact continuous level measurement in liquids, especially suited for small process connections and for chemically aggressive media; Rod antenna with PTFE coating |
|
| Supply / Communication |
2-wire (HART / PROFIBUS PA/ FOUNDATION Fieldbus) 4-wire (HART) |
|
| Frequency | C-band (~6 GHz) | |
| Accuracy | +/- 6 mm (0.24 in) | |
| Ambient temperature |
-40...+80 °C (-40...+176 °F) |
|
| Process temperature |
-40...+150 °C (-40...+302 °F) |
|
| Process pressure absolute / max. overpressure limit |
Vacuum...40 bar (Vacuum...580 psi) |
|
| Main wetted parts | PTFE, PVDF | |
| Process connection |
Thread: MNPT 1 1/2, R 1 1/2 Flange: DN50...DN150, ASME 2"...6", JIS 10K |
|
| Max. measurement distance | 20 m (65 ft) | |
![]() |
![]() |
|
| Output |
4...20 mA HART PROFIBUS PA FOUNDATION Fieldbus |
|
| Certificates / Approvals |
ATEX, FM, CSA, CSA C/US, IEC Ex, NEPSI, INMETRO, KC Overfill prevention WHG SIL EN 10204-3.1 |
|
| Options |
Display, Customized parameterization Gas-tight feed through PWIS free |
|
| Specialities |
SIL 2 according to IEC 61508, Safety and reliability with Multi-Echo Tracking, HistoROM |
|
| Application limits |
Maximum measuring range is dependent on the tank form and/or application
Nozzle height >250 mm: |
|